Secondary Injection Relay Testing Kit
The single phase relay test set should be suited for the testing and adjustments of all the types of production and distribution relays. In addition to the above, it should also test converters and energy meters.
Salient Features:
· All outputs continuously variable.
· Time base multi range DIGITAL TIMER
· True RMS digital metering of outputs
· Compact rugged design
· All current outputs fully isolated and distortion free.
· Suitable for testing thermal devices
· All controls and metering centralized.
GENERAL SPECIFICATIONS | |
Power Supply | Mains supply: 220 V ± 15%; 50-60 Hz. |
Main Generator | The main generator shall have three outputs: currents, voltage AC, voltage DC with provision of generating at maximum power or at reduced power. On all outputs the capability of - Current Ranges: 10, 40, 100 A. Output power: 800 VA. AC voltage range: 250 V. Output power: 500 VA. DC voltage range: 300 V. Output power: 300 W. |
Auxiliary AC Voltage | Output ranges: 65 – 130 - 260 V. Output power: 30 VA. |
Auxiliary DC Voltage | Ranges: 130 V and 240 V. Power: 90 W at full range; max. currents: 0.9 A @ 130 V and 0.45 A @ 240 V. |
Timer | The timer shall have two inputs, START and STOP. Inputs level: Normal Open or Normal Close. Clean or under voltage, maximum 275 V DC. Timer ranges: 9.999 s; 99.99 s; 99999.9 s. Accuracy: ± 0.005% of value ± 0.01% of range. |
Auxiliary Contact | Two auxiliary make and break contacts shall have a delay from 0 to 99.99 s with respect to test start. Contacts characteristics: 5 A; 250 V AC; 120 V DC |
Output Measurement | The display: AC current (AC or DC voltage); auxiliary AC voltage; auxiliary DC voltage. Accuracy, DC: 0.5% of reading ± 0, 1% of range; AC: 1% of reading ± 0,2% of range. |
External Input Measurement | Input current ranges. 20 mA or 10 A, AC or DC. Accuracy, DC: 0.5% of reading ± 0,1% of range; AC: 1% of reading ± 0,2% of range. Maximum input voltage: 600 V, AC or DC. |
Test Control | Selections, for the test of over- or under-(current, voltage.) relays. . OFF: main outputs not generated;. ON: all outputs generated;. From OFF to ON + time: all outputs shall be generated and timer shall start; at STOP, outputs are removed and time shall be displayed. . From ON to OFF + time: outputs shall be removed and timer shall start; at STOP, the time shall be displayed. - Reclose test. |
Product Details:
Minimum Order Quantity | 1 Piece |
Brand | Pragati Process Controls |
Model | SCI |
Secondary Injection Kit
It is a method of connecting a secondary injection test set to a trip unit (trip device, over current module, protection device, OCR, ETU etc.) on a circuit breaker and injecting a simulated current to prove it works at different levels.
Salient Features:
· All outputs continuously variable.
· Time base multi range DIGITAL TIMER
· True RMS digital metering of outputs
· Auto-switch off in all modes of operation.
· All current outputs fully isolated and distortion free.
· Suitable for testing thermal devices
· All controls and metering centralized.
General Specification | |
Supply Input | Three Phase 380 to 440V AC 50Hz ±10%, Mains MCB to Power ON the Panel |
Output Voltage Range: | 0 to 300 V (L-N) or 0 to 520 Phase to Phase , 3 knobs to control individual voltage magnitude |
Output Current Range: | 0 to 5.0 Amp AC per phase |
Frequency: | 45 to 60 Hz |
Output ports: | Vr ,Vy, Vb - N, Ir (Hi, Lo),Iy (Hi, Lo),Ib (Hi, Lo) |
Compliance: | 40 VA, at FS on V ranges & on A channels |
Accuracy: | Class 0.25% (for V, A, W and Whr ) |
Sinusoidal Outputs: | THD 1.5% |
Protections: | Overload and Short circuit |
Setting: | Setting: By coarse and fine set of potentiometer for Voltage and Current |
Digital Timer: | With External Start / Stop Signal Input facility Resolution 1 m Sec Auto ranging model Select- TI103C (48*96) |
Phase Seq: | Phase Seq indicator with ext. input.- minilec- |
Amp meter: | 4-20 Mille amp meter for Transducer output measurement |
Fabrication | Enclosure is Powder coated sheet steel SWG 16 with lifting handles |
Dimension : | (500W X 200H X 450D)mm. |
Weight : | Weight of equipment Approx. 40 Kg. |
Wiring | LFH Black wire to be used |
Product Details:
Brand | Pragati Process Controls |
Model | SCI |
Three Phase Secondary Injection Kit
Secondary injection tests are performed to verify the correct operation of the protection system with regard to everything that is connected to the secondary of the transformers. The secondary protection system may include Protective Relays, auxiliary relays, protection circuits, communications and control systems, metering devices, low-voltage devices, alarms, etc. Accordingly, the secondary injection test covers not only the testing of protective relays and their tripping settings, but also the checking of all associated circuits and devices involved in the proper performance of the secondary protection system.
Salient Features
General Specification : 3 Phase Relay Protection Tester | |
Supply power | AC 220V±10%,50/60Hz |
Alternating Current Output: |
|
Output accuracy | 0.5 magnitude |
Phase current output | 0~40A, Three parallel phase current output 0~120A |
Phase current value with long time under permission | 10A |
Phase current maximum power output | 420VA, Three parallel phase current maximum power output 900VA |
Three parallel phase current maximum work time | 10s |
Harmonic frequency number | 1~20 time(s) |
Direct Current Output |
|
Current output | 0~±10 A/each phase, 0~±30 A/every three parallel |
Maximum output of load voltage | 20v |
Alternating Voltage Output: |
|
Phase voltage output (RMS) | 0~120v |
Line voltage output (RMS) | 0~240v |
Phase voltage/line voltage power output | 80VA/100VA |
Output accuracy | 0.5 magnitude |
Harmonic frequency number | 1~20 time(s) |
Direct voltage output: |
|
Phase voltage output amplitude | 0 ~ +160v |
Line voltage output amplitude | 0 ~ +320v |
Phase voltage/line voltage power output | 70VA/140VA |
Product Details:
Minimum Order Quantity | 1 Unit |
Brand | Pragati Process Controls |
Model | SCI |
Secondary Current Injection Source
The secondary protection system may include Protective Relays, auxiliary relays, protection circuits, communications and control systems, metering devices, low-voltage devices, alarms, etc. Accordingly, the secondary injection test covers not only the testing of protective relays and their tripping settings, but also the checking of all associated circuits and devices involved in the proper performance of the secondary protection system.
Salient Features:
General Specification | |
Input voltage | Three Phase 415V AC 50Hz (2 A at Full load) ±10% |
CT Test Current | 0-1A & 0-5A & 0-10A Continuously Variable (Three O/p Simultaneously) Suitable to test max range of 20VA CTOutput R, Y, B Phases and neutral is provided with ON/OFF facility (for various fault simulations as 3Ø & N, 2Ø & N, 1Ø & N, only 3Ø, only 2Ø etc. Digital timer for switching time measurement in milliseconds. Resolution 0.01 Sec. it will start count till aux contact is open 3 ½ Digital Ammeter 0-10A |
PT Test Voltage | 0-220V AC Between R-N,Y-N,B-Continuously Variable. With the help of Manual Auto Transformer. Each phase require separate single phase auto transformer |
DC Voltage For Numerical Relay Testing | Output voltage 5-230V DC Output current 0-5A Output Ripple CV 5mV RMS maximum Metering 3½ digit AC Ammeter, 3½ digit AC Voltmeter Protection Output overload protection Output short circuit protection Output overvoltage trip |
Single phase Output | Fix output protected with two pole MCB, Emergency Stop on front of Control Trolley |
Fabrication | Robust enclosure M S Powder Coated & mounted on lockable swiveling PU 4 inch castors. |